Fire protection

Fireproof installations for individual pipes and pipe routes of R30 – R120 and F30 – F120. Proof of compliance with the criteria according MLAR (German standard pipe system directive) for installation in escape and rescue routes.Additionally, the same information is documented in the inspection reports for a fire resistance rating of R30, R60, R90 and R120 according to EN1363-1 and DIN4102-2.

Fire protection inspections for SaMontec products.

Product Document no. MLAR R30 – R120 F30 – F120
FRS MPA Braunschweig – 3649/384/12
FUS MPA Braunschweig – 3147/252/12
FCA MPA Braunschweig – 3147/252/12
SB MPA-NRW – 210005109-7
SBS MPA-NRW – 210005109-4
PDH-K MPA-NRW – 210005109-6

Fire protection – protection goals.

Firstly, fire protection serves to protect people, and is regulated by the building laws in the respective countries (or regional states). Secondly, fire protection serves to protect property and this is regulated by the insurance associations, such as VdS and FM. These requirements partially go beyond the building legislation. This is particularly evident in the installation of fire protection systems, such as sprinklers, etc., as approved or recognised components must be used here.

Fire inspection reports for the mounting of pipe clamps and mounting rails..

The fire safety inspection reports presented here meet the requirements for fire protection according to the building regulations of the countries and, especially for Germany, according to the nationwide homonymic German pipe systems directive (LAR), based on the standard pipe systems directive of 2005 (MLAR 2005).
Personal protection is defined in the MLAR Directive through clear rules for escape routes, such as corridors, stairwells, and hallways between stairwells and the exit.
The key message is to ensure the safety of the escape route by ensuring the functioning of the fire-proof sub-ceiling. To this end, compliance with the minimum distance of min a ≤ 50 mm according to MLAR is required between installations and underlying suspended fire-proof F30 sub-ceilings (fire resistance of 30 minutes). Based on the fire inspections, load information for a fire resistance of 30 minutes in relation to the maximum permissible deformation of mounting rails or pipe clamps, for example, was determined. The necessity for these considerations arises from the properties of the steel, which is subjected to a temperature of > 800°C according to the standard temperature curve (ISO curve). Additionally, the same information is documented in the inspection reports for a fire resistance rating of R30, R60, R90 and R120 according to EN1363-1 and DIN4102-2.

Dependency of the yield strength, proportional limit and elasticity module on the temperature (basis: EN1993-1-2:2012-12 Eurocode 3).

fischer Installation grid

Our flexible system opens up room for your creativity

More information

Fire protection

Fireproof Pipe Mounting

More information

fixings for sprinkler systems

Your safety in the installation.

More information